Conference article

Tube-fin Heat Exchanger Circuitry Optimization For Improved Performance Under Frosting Conditions

Zhenning Li
Center for Environmental Energy Engineering, University of Maryland College Park, MD 20742 USA

Hongtao Qiao
Mitsubishi Electric Research Labs, 201 Broadway Cambridge, MA 02139 USA

Vikrant Aute
Center for Environmental Energy Engineering, University of Maryland College Park, MD 20742 USA

Download articlehttp://dx.doi.org/10.3384/ecp19157259

Published in: Proceedings of the 13th International Modelica Conference, Regensburg, Germany, March 4–6, 2019

Linköping Electronic Conference Proceedings 157:27, p. 6

Show more +

Published: 2019-02-01

ISBN: 978-91-7685-122-7

ISSN: 1650-3686 (print), 1650-3740 (online)

Abstract

Frost accumulation on tube-fin heat exchanger leads to reduction in evaporator capacity and deteriorates cycle efficiency. The conventional counter-flow heat exchanger circuitry has the disadvantage that more frost tends to accumulate in the first few banks exposed to the incoming air. This frost concentration makes the air side flow resistance increase rapidly, thus reduces the air flow rate and evaporator capacity under constant fan power. In this paper, a novel integer permutation based Genetic Algorithm is used to obtain optimal circuitry design with improved HX performance under frosting conditions. A dynamic HX model with the capability to account for non-uniform frost growth on a fan-supplied coil is used to assess the performance of optimal circuitry. The case study shows that the proposed circuitry design approach yields better circuitry with larger HX capacity, more uniform frost distribution, less air flow path blockage, and therefore longer evaporator operation time between defrost operations.

Keywords

Heat Exchanger, Frost Growth, Circuitry Optimization, Genetic Algorithm

References

No references available

Citations in Crossref