Conference article

Experimental Ground Source Heat Pump System to Investigate Heat Transfer In Soil

Hakan Demir
Yildiz Technical University, Istanbul, Turkey

S. özgür Atayilmaz
Yildiz Technical University, Istanbul, Turkey

Özden Agra
Yildiz Technical University, Istanbul, Turkey

Download articlehttp://dx.doi.org/10.3384/ecp110571352

Published in: World Renewable Energy Congress - Sweden; 8-13 May; 2011; Linköping; Sweden

Linköping Electronic Conference Proceedings 57:16, p. 1352-1359

Show more +

Published: 2011-11-03

ISBN: 978-91-7393-070-3

ISSN: 1650-3686 (print), 1650-3740 (online)

Abstract

The earth is an energy resource which has more suitable and stable temperatures than air. Typical values for Coefficient of Performance (COP) of Ground Source Heat Pumps (GSHPs) are up to 8 while it is 4 of air source heat pumps. GSHPs were developed to use ground energy for residential heating. The most important part of a GSHP is the Ground Heat Exchanger (GHE) that consists of pipes buried in the soil and is used for transferring heat between the soil and the heat exchanger of the GSHP. Soil composition; density; moisture and burial depth of pipes affect the size of a GHE. Design of GSHP systems in different regions of US and Europe is performed using data from an experimental model. However; there are many more techniques including some complex calculations for sizing GHEs. An experimental study was carried out to investigate heat transfer in soil. Measured fluid inlet temperatures were used in the numerical simulation and the fluid outlet temperatures were calculated. A parametrical study was conducted to investigate effects of soil thermal properties and geometrical parameters on heat transfer from ground heat exchanger. It is seen that the soil thermal conductivity has great importance on heat transfer. Also; burial depth and distance between pipes are other parameters to be considered for sizing GHEs.

Keywords

Ground source heat pump; Parallel pipe horizontal ground heat exchanger; Numerical solution

References

[1] B. Bohm; On transient heat losses from buried district heating pipes; Int. Journal of Energy Research 24 (2000); pp. 1311-1334 doi: 10.1002/1099-114X(200012)24:15<1311::AID-ER648>3.0.CO;2-Q.

[2] M. Chung; P.S. Jung; R.H. Rangel; Semi-analytical solution for heat transfer from a buried pipe with convection on the exposed surface; Int. Journal of Heat and Mass Transfer 42 (1999); pp. 3771-3786 doi: 10.1016/S0017-9310(99)00046-0.

[3] Y. Gu; D.L. O’Neal; An analytical solution to transient heat conduction in a composite region with a cylindrical heat source; Transactions of the ASME 117 (1995); pp. 242-248

[4] M.A. Hastaoglu; A. Negiz; R.A. Heidemann; Three-dimensional transient heat transfer from a buried pipe – part III comprehensive model; Chemical Engineering Science 50 (1995); pp. 2545-2555 doi: 10.1016/0009-2509(95)00111-H.

[5] T.K. Lei; Development of a computational model for a ground-coupled heat exchanger; ASHRAE Transactions: Research 99 (1993); pp. 149-159

[6] V.C. Mei; Heat transfer of buried pipe for heat pump application; Journal of Solar Energy Engineering 113 (1991); pp. 51-55 doi: 10.1115/1.2929951.

[7] P.D. Metz; A Simple computer program to model three-dimensional underground heat flow with realistic boundary conditions; Transactions of the ASME 105 (1983) ); pp. 42-49

[8] S. Mukerji; K.A. Tagavi; W.E. Murphy; Steady-state heat transfer analysis of arbitrary coiled buried pipes; Journal of Thermophysics and Heat Transfer 11 (1997); pp. 182-188 doi: 10.2514/2.6250.

[9] A. Negiz; M.A. Hastaoglu; R.A. Heidemann; Three-dimensional heat transfer from a buried pipe – I. laminar flow; Chemical Eng. Science 48 (1993); pp. 3507-3517 doi: 10.1016/0009-2509(93)85006-B.

[10] A. Negiz; M.A. Hastaoglu; R.A. Heidemann; Three-dimensional transient heat transfer from a buried pipe: solidification of a stationary fluid; Numerical Heat Transfer 28 (1995); pp. 175-193 doi: 10.1080/10407789508913740.

[11] M. Piechowsky; Heat and mass transfer of a ground heat exchanger: theoretical development; Int. Journal of Energy Research 23 (1999); pp. 571-588 doi: 10.1002/(SICI)1099-114X(19990610)23:7<571::AID-ER462>3.0.CO;2-6.

[12] A.D. Chiasson; Advances in Modeling of ground source heat pump systems; MSc Thesis; Oklahoma State University; 1999

[13] M. Piechowski; A ground coupled heat pump system with energy storage; PhD Thesis; The University of Melbourne; 1996

[14] H. Demir; A. Koyun; G. Temir; "Heat Transfer of Horizontal Parallel Pipe Ground Heat Exchanger and Experimental Verification"; Applied Thermal Engineering 29 (2009); pp. 224-233 doi: 10.1016/j.applthermaleng.2008.02.027.

Citations in Crossref